Accelerated Loss of Mains Change Programme (ALoMCP)

九州bet9备用网址following the investigation into 9 august 2019 power outage, approximately 550mw of embedded generation was disconnected. in some cases, due to the expected operation of the rate of change of frequency protection system but in other cases because some generators may be operating incorrect protection settings.

to avoid future outages, the alomcp was initiated to amend the loss of mains (lom) settings on generation in gb. in summary these are to remove vector shift (vs) as an allowable lom (loss of mains) technique, and to change any rate of frequency protection (rocof) settings to new, less sensitive values or even disable it.

the vast majority of the sma inverters do not rely on rocof or vs techniques. for that reason, only the following string inverters are on scope of the alomcp.

  • MLX / STP 60-10
  • SHP75-10
  • TLX+6K, TLX Pro+6K, TLX 8K, TLX Pro 8K, TLX+8K, TLX Pro+8K, TLX 10K, TLX Pro 10K, TLX+10K, TLX Pro+10K
  • FLX Pro 17, FLX Pro 15

for the mlx/stp 60-10 and shp75-10, we have defined three country settings for the uk. two of them contain rocof settings in accordance with the g59/3. similarly, for the inverters tlx and flx, the country setting contains rocof settings in accordance with the g59/3. for these inverters, the rocof settings need to be changed or set to disabled as specified in the alomcp.

please refer to the table below to see if you are affected by the alomcp and to see what action, if any is needed.

九州bet9备用网址further guidance will be given for the install base of central inverters in due course.

SMA inverter families and their means of disconnection from the public grid

Inverter Type RoCoF or Vector shift used Action Required
SMA    
STP3.0-3AV-40 -
STP10-3AV-40
No None
STP 5000TL-20 -
STP 120000TL-20
No None
STP 10000TL-10 -
STP 17000TL-10
No None
STP 15000TLEE-10 -
STP 20000TLEE-10
No None
STP 15000TL-30 -
STP 25000TL-30
No None
STP 20000TL-30 No None
STP 25000TL-30 No None
STP 50-40 No None
STP 60-10 Yes Contact SMA Service line
SHP 75-10 Yes Contact SMA Service line
SHP 100-20 - SHP 150-20 No None

Inverter Type RoCoF or Vector shift used Action Required
Danfoss    
TLX 6K - TLX 10K Yes Contact SMA Service line
TLX+6K - TLX+10K Yes Contact SMA Service line
TLX Pro +6K - TLX Pro +10K Yes Contact SMA Service line
FLX Pro 15 - FLX Pro 17 Yes Contact SMA Service line
MLX 60 Yes Contact SMA Service line